What Size Water Line Do I Need? Supply Pipe Size Calculator

What size water line does a house need? Count the fixtures for peak gallons per minute to get the smallest main that holds speed and pressure.

Water Supply Pipe Size Calculator

Fixture units to peak flow and a main size
Toilet (tank)2
Bathroom sink2
Bathtub or tub shower1
Kitchen sink1
psi
1 inch
Minimum main size
19.3 GPM
Peak demand from 19.5 fixture units

About 33 psi left at the highest fixture at peak flow.

  • A 3/4 inch main would push water at about 12.8 feet per second, faster than the 10 commonly allowed for a cold-water line.
  • Over 80 feet of pipe (about 120 feet once fittings are counted), friction in a 1 inch main takes about 12.4 psi at peak flow.
  • This holds back about 8 psi for the water meter and backflow preventer. On a well with neither, there is a little more to spare.
  • If the main is PEX and the run is long or the house is tall, check one size up. PEX has a smaller bore than copper of the same size, so it loses more pressure.
  • Hunter's method dates from 1940 and can run high for today's low-flow fixtures, so this leans toward the larger size.

An estimate from Hunter fixture units and pipe friction. A licensed plumber confirms the main size against your water pressure, meter and local code.

The results on this page come from public data and general rules of thumb, applied to what you entered. They can be wrong or out of date, and they may not fit your home. They are not professional advice, an inspection or an offer of service. Before you act on anything here, check it with a licensed pro or the agency named on the page. Any decision you make is your own, and we are not responsible for losses from relying on these results.

Data: supply fixture units and demand curve from NBS BMS 65 (Hunter, 1940) · Hazen-Williams friction for copper tube · this tool's own allowances from common plumbing practice: 10 feet per second top water speed, 8 psi for the meter and backflow preventer, 15 psi at the top fixture and fittings as half again the pipe length · Updated November 2026

How to size a water supply line for a house

Supply fixture units and peak demand in GPM

Each fixture gets a supply fixture unit value: a toilet 3, a tub or shower 2, a bathroom sink 1. Hunter's demand curve from 1940 turns the total into a peak flow in gallons per minute, the most the house is likely to draw at once.

Speed limits for water in a pipe

Cold water service lines are commonly held to 10 feet per second or less. Above about 8, water in a pipe gets noisy, causes water hammer and wears fittings faster. The main has to carry the peak flow under the 10 limit.

Pressure lost to height, the meter and pipe length

Every foot of rise uses 0.43 psi. The water meter and backflow preventer take about 5 to 10 psi at peak flow, and this tool holds back 8. Friction in the pipe and fittings takes more as flow goes up. What is left at the highest fixture has to be about 15 psi or more for showers and faucets to work. A long run or low street pressure can push the main up a size.

Water line size questions

What size water line does a house need?

It depends on the fixtures, the pressure and how far the water travels. A toilet, bathroom sink, tub and kitchen sink at 60 psi over a 60 foot run come out at 3/4 inch here. The two-bath house the tool opens with, at the same pressure over 80 feet, comes out at 1 inch.

Is a 3/4 inch or 1 inch water main better?

A 1 inch main carries about 70% more flow than a 3/4 inch at the same speed, which keeps pressure up when two showers and the washer run together. A plumber checks that against the size of the meter and the service line from the street.

Does pipe length affect water pressure?

Yes. Friction takes pressure along every foot of pipe and every fitting, and the loss climbs quickly as flow goes up. This tool counts the fittings as half again the pipe length, so 80 feet of pipe is figured as 120.

What water pressure should a house have?

The model plumbing codes cap house pressure at 80 psi, so above that a pressure reducing valve goes in. Lower pressure leaves less to spend on height and friction, which this tool shows as the psi left at the highest fixture.