Duct Size Calculator (Ductulator) by CFM and Friction Rate
Type your CFM into this ductulator for the round duct size, the matching rectangular sizes and the air speed, with a check for duct noise.
The results on this page come from public data and general rules of thumb, applied to what you entered. They can be wrong or out of date, and they may not fit your home. They are not professional advice, an inspection or an offer of service. Before you act on anything here, check it with a licensed pro or the agency named on the page. Any decision you make is your own, and we are not responsible for losses from relying on these results.
Data: Darcy-Weisbach friction for galvanized round duct (published power-law fit); Huebscher equal-friction rectangular equivalent. The quiet air speed limits (700 fpm branches, 900 fpm trunks, 600 fpm returns), the 1.5x friction for flex, the 5% rounding to a standard size and the 10% cut-off for rectangular heights are this tool’s own design values · Updated November 2026
How to size a duct by CFM
CFM and friction rate set the duct size
Air rubbing on the inside of a duct loses pressure. The friction rate is how much pressure the system can spend per 100 feet of duct, in inches of water. Pick an airflow and a friction rate, and the equal-friction method gives the round size that loses that much. The choices here run from 0.05 to 0.10.
Sizing flex duct compared with metal
Flex duct has a ribbed inner wall that drags on the air more than smooth metal, so the same airflow needs a larger flex duct. Flex that sags or gets pinched drags far more than flex pulled tight, and an HVAC contractor looks for that when a room gets weak airflow.
Duct air speed and noise limits
Air that moves too fast whistles at the registers. For a quiet home system, this tool keeps supply branches under about 700 feet per minute, supply trunks under about 900 and returns under about 600. The result shows the speed in the standard size and flags it when it runs over.
Questions about duct size and CFM
What size duct do I need for 400 CFM?
About a 10 inch round metal duct at a 0.08 or 0.10 friction rate, which matches a 12 x 8 inch rectangular duct. At 0.05 it takes a 12 inch, and so does flex at 0.08. In a 10 inch duct that much air moves about 730 feet per minute, over the branch limit and under the trunk limit.
Is there a duct size chart by CFM?
At the starting friction rate of 0.08, round metal duct works out to about 6 inch for 100 CFM, 8 inch for 200, 9 inch for 300, 10 inch for 400, 12 inch for 600, 14 inch for 800 and 16 inch for 1,200. Flex duct and lower friction rates need a bigger size. Enter your CFM above for the exact size and the matching rectangular duct.
How much CFM does a 6 inch duct carry?
Roughly 100 CFM in metal at a 0.08 friction rate, and a bit less in flex. At 100 CFM the air in a 6 inch duct moves about 510 feet per minute, under the 700 fpm branch limit.
What friction rate should I use for duct design?
It depends on the blower and the longest run in the house. An HVAC contractor works it out from the pressure the blower can deliver after the coil, filter and registers take their share. This tool starts at 0.08, the middle of its three choices.
How do I convert round duct to rectangular?
Two ducts that lose the same pressure at the same airflow are equivalent. The tool uses the published equal-friction formula to list rectangular sizes at 6, 8, 10 and 12 inch heights that match the round size. It skips a height when even a square duct that tall would be more than 10% bigger than the round duct.
Why is my duct noisy?
Air moving too fast for the duct size is one cause. A register that is too small or partly closed is another. An HVAC contractor measures the airflow and the static pressure to find which.